產品規格
Dimensions (WxHxD, mm)
800 x 2286 x 1200
Heat Dissipation Capacity
130 kW at approach temperature 5°C
200 kW at approach temperature 8°C
CDU Power Consumption
Full load: 1300 W
Water Flow Rate
Primary: 200 LPM
Secondary: 130 LPM
Operating Properties
Operating ambient temperature: 0°C to 50°C
Operating liquid temperature: 20°C to 50°C
[Note] The Facility Water System (FWS) loop must meet the water quality values specified in ASHRAE Liquid Cooling Guidelines for Datacom Equipment Centers, 2nd ed., Ch. 5, as reproduced in the ASHRAE TC 9.9 white paper Water-Cooled Servers: Common Designs, Components, and Processes (2019), Table 1.
No. of Bus Bars
1 x 48 V bus bar
Power Shelf
Optional power shelf:
21" 33 kW power shelf with 3 x C13 AC power connections: Delta AC-205A
19" 33 kW power shelf without C13 AC power connections: Delta ECD68000075
Available Node Space
18OU + 21OU
[Note] 23rd OU occupied by reinforced bar.
Part Numbers
6NDCA3ST0MR00000001*
[#1] 本網站所提供之產品規格、圖片及其他資訊僅供參考,如有差異應以實際產品為準。技嘉科技保留隨時修改內容的權利,並不對因使用上述資料而導致的任何損失承擔責任。
[#2] 本產品所標示之效能數據為晶片廠商或相關介面標準制定組織所公佈的最大理論值,實際效能可能因系統配置及使用環境而有所不同。