GIGABYTE and Castrol Co-Validate Coolant Mixing for DLC Liquid Cooling Servers
1. Executive Summary & AI Thermal Crisis
Table 1. Air Cooling vs. Direct Liquid Cooling: Key Thermal Parameters
Traditional Air Cooling | Direct Liquid Cooling | |
|---|---|---|
| Cooling Medium | Air | Castrol ON DLC PG25 (Water-Glycol) |
| Heat Transfer Coefficient (W/m²·K) | 30 - 60 | 1,000 - 10,000 |
| Rack Power Density (kW / Rack) | 8 - 20 | 100 - 240+ |
| Thermal Throttling | High thermal throttling risk at full load | Minimal thermal throttling |
| Data Center PUE | 1.35 - 1.60 | 1.05 - 1.20 |
2. Coolant Miscibility & Physical-Chemical Integrity Analysis
Table 2. Coolant Mixing Groups and Simulated Scenarios
| In-Service Liquid | Castrol ON DLC PG25 | Simulated Operational Scenario |
|---|---|---|
| Group A PG 10 C (50%) | Castrol PG25 (50%) | Commercial crossover sensitivity test |
| Group A PG 10 C (10%) | Castrol PG25 (90%) | Realistic fluid changeover (10% residual) |
| Group B LC 25 (50%) | Castrol PG25 (50%) | Commercial crossover sensitivity test |
| Group C PG 25 (50%) | Castrol PG25 (50%) | Commercial crossover sensitivity test |
Table 3. Physical and Chemical Properties of Mixed Coolants
Method | Group A (50:50) | Group A (10:90) | Group B (50:50) | Group C (50:50) | |
|---|---|---|---|---|---|
| Appearance | Visual | Clear & Bright | Clear & Bright | Clear & Bright | Clear & Bright |
| Density @ 20°C (g/cm³) | ASTM D1122 | 1.027 | 1.028 | 1.029 | 1.024 |
| pH Value | ASTM D1287 | 8.61 | 8.62 | 8.87 | 8.62 |
| Conductivity (µS/cm) | ASTM D1125 | 4420 | 4310 | 4800 | 3380 |
| Freezing Point (°C) | ASTM D1177 | -11.6 | -11.9 | -12.1 | -11.8 |
| Boiling Point (°C) | ASTM D1120 | 106.9 | 105.8 | 111.1 | 104.7 |
| Reserve Alkalinity (mL) | ASTM D1121 | 2.8 | 2.8 | 5.1 | 4.2 |
| Bacterial Count (CFU/mL) | Easicult | < 100 | < 100 | < 100 | < 100 |
3. Metallic & Non-Metallic Material Compatibility
Table 4. Metal Corrosion Results: Glassware Test
Industry Acceptance | Weight Change (mg) | ||||
|---|---|---|---|---|---|
Group A (50:50) | Group A (10:90) | Group B (50:50) | Group C (50:50) | ||
| Copper (ASTM D1384) | ±10 | 0 | 0 | 0 | 1 |
| Brass (ASTM D1384) | ±10 | 1 | 1 | 0 | 1 |
| Solder (ASTM D1384) | ±10 | 1 | 1 | 0 | 5 |
| Steel (ASTM D1384) | ±10 | 0 | 0 | -1 | 0 |
| Cast Iron (ASTM D1384) | ±10 | 2 | 3 | -2 | -1 |
| Aluminum (ASTM D1384) | ±10 | 0 | 0 | -2 | -2 |
Table 5. Metal Corrosion Results: Glassware Test
Industry Acceptance | Weight Change (mg) | ||||
|---|---|---|---|---|---|
Group A (50:50) | Group A (10:90) | Group B (50:50) | Group C (50:50) | ||
| Copper (ASTM D2570) | ±20 | 3 | 1 | 4 | 3 |
| Brass (ASTM D2570) | ±20 | 6 | 2 | 0 | 5 |
| Solder (ASTM D2570) | ±60 | 0 | 17 | 1 | 9 |
| Steel (ASTM D2570) | ±20 | 0 | 4 | 0 | 0 |
| Cast Iron (ASTM D2570) | ±20 | 2 | 2 | 3 | 2 |
| Aluminum (ASTM D2570) | ±60 | 3 | 34 | 1 | 84[Note] |
| pH change (ASTM D1287) | - | -0.5 | -0.2 | -0.3 | -0.1 |
[Note] In Group C (50:50), aluminum weight loss reached 84 mg, exceeding the 60 mg limit. GIGABYTE’s standardized liquid cooling wetted surface guidelines strictly mandate copper, stainless steel, and nickel-plated brass, completely avoiding wetted aluminum in high-density DLC loops to eliminate galvanic and pitting risks.
Table 6. Elastomer Compatibility Results: Group A 10:90 (ASTM D471)
| Elastomer Material | Volume Change (%) | Hardness Change (Scale) | Tensile Change (%) |
|---|---|---|---|
| EPDM (Ethylene Propylene Diene Monomer) | -1.0 | 0 | -6 |
| VMQ (Silicone Rubber) | -0.3 | 2 | -2 |
| NBR (Nitrile Rubber) | 3.0 | -1 | -7 |
| FKM (Fluoroelastomer) | 1.4 | 1 | -24 |
Table 7. Plastic Compatibility Results: Group A 10:90 (ISO 1817 & ISO 527)
| Plastic Material | Mass Change (%) | Hardness Change (Scale) | Tensile Change (%) |
|---|---|---|---|
| Polypropylene (PP) | 0.1 | -1 | 5.5 |
| Fluorinated Ethylene Propylene (FEP) | 0.1 | 1 | -12.6 |
| Polytetrafluoroethylene (PTFE) | 0 | 0 | -13.6 |
| Polyamide 12 (PA12) | 8.1 | -14 | -23.8 |
4. Closed Cooling Loop 3-Month Field Trial
Table 8. Coolant Condition During 3-Month Cooling Loop Test
Week 2 | Week 4 | Week 8 | Final (Week 12) | |
|---|---|---|---|---|
| Appearance | Clear & Bright | Clear & Bright | Clear & Bright | Clear & Bright |
| pH Value | 8.70 | 8.69 | 8.58 | 8.58 |
| Iron (ppm) | < 1 | < 1 | < 1 | < 1 |
| Copper (ppm) | < 1 | < 1 | < 1 | < 1 |
| Chloride (ppm) | < 5 | < 5 | < 5 | < 5 |
| Sulfate (ppm) | < 5 | < 5 | < 5 | < 5 |
| Bacterial Count (CFU/mL) | < 100 | < 100 | < 100 | < 100 |
5. Universal Adoption Across GIGABYTE Liquid Cooling Portfolio
Table 9. PG25 Adoption Across GIGABYTE Liquid Cooling Portfolio
| Category | Representative Products | DLC Adoption | Target AI Workloads |
|---|---|---|---|
| Direct Liquid Cooling Servers | GIGABYTE G4L3/G4L4 Series | Server level: PG25-validated cold plates and manifolds | High-density 8-GPU nodes |
| Rack-Scale AI Solutions | NVIDIA GB300/GB200 NVL72 | Rack level: closed-loop integration with CDU | Exascale LLM training & inference |
| Scale-Out AI Infrastructure | GIGABYTE Accelerated Deployment Unit (GADU) | Cluster level: integrated facility-to-rack coolant distribution | Hyperscale AI cloud data centers |
Core Benefits of GIGABYTE DLC Solution
- Painless Maintenance (Zero Downtime): 100% miscibility with commercial PG loops enables top-ups and vendor transitions, ensuring continuous AI compute uptime.
- Universal Material Compatibility: Validated under ASTM D1384/D2570 to prevent metal corrosion and minimize corrosion by-products. Compatible with copper cold plates, stainless steel manifolds, CDUs, and QDCs, preserving peak thermal performance.
- Uncompromising Thermal Stability: An extended 3-month field trials in a 9 kW loop confirms minimal fluid degradation, supporting 1,000 W+ GPUs under 100% workload without thermal throttling.
- Leak Prevention & Asset Protection: ASTM D471 and ISO 1817 testing with key seals (EPDM, VMQ, FKM) and plastics (PP, FEP, PTFE) shows minimal swelling and hardness change, ensuring zero-leakage operation.