Specifications
Dimensions (WxHxD, mm)
800 x 2286 x 1200
Heat Dissipation Capacity
24 kW at 10°C approach temperature
CDU
20U Liquid-to-Air
Power consumption: 4.5 kW at full load
AC Input:
- 208-230 V, 1-phase, 50/60 Hz
- 90-264 V, 1-phase, 50/60 Hz per inlet
Liquid Flow Rate
Secondary: 36 LPM
Manifold
38 pairs of UQD06 supply/return connectors
Operating Properties
Operating ambient temperature: 0°C to 50°C
PDU
1 x PDU for EIA switch
AC Input:
- IEC 60309 3P+N+E 6h plug, 200-240/346-415 V, 50/60 Hz, 48 A max
AC Output:
- 9 x C13/C15/C19 combo, 200-240 V, 16 A max per outlet, 48 A max per phase
No. of Bus Bars
1 x 48 V bus bar
Power Shelf
2 x 19" 33 kW power shelves with 6 x 5.5 kW power supplies
AC Input:
IEC 60309 3P+N+E 6h plug, 200-240/346-415 V, 50/60 Hz, 60 A max
Part Numbers
6NDCA31B0MR00000001*