Specifications
Dimensions (WxHxD, mm)
800 x 2286 x 1200
Heat Dissipation Capacity
130 kW at approach temperature 5°C
200 kW at approach temperature 8°C
CDU Power Consumption
Full load: 1300 W
Water Flow Rate
Primary: 200 LPM
Secondary: 130 LPM
Operating Properties
Operating ambient temperature: 0°C to 50°C
Operating liquid temperature: 20°C to 50°C
No. of Bus Bars
1 x 48 V bus bar
Power Shelf
Optional power shelf:
21" 33 kW power shelf with 3 x C13 AC power connections: Delta AC-205A
19" 33 kW power shelf without C13 AC power connections: Delta ECD68000075
Available Node Space
18OU + 21OU
[Note] 23rd OU occupied by reinforced bar.
Part Numbers
6NDCA3ST0MR00000001*
[#1] All materials provided herein are for reference only. GIGABYTE reserves the right to modify or revise the content at any time without prior notice.