A1P0-EA0

12U EIA Tank
  • Supports up to 12U EIA servers
  • Minimum PUE reaching 1.02
  • Up to 40 kW of heat dissipation capacity
  • Supports server length up to 900 mm
Ordering Numbers: 6NA1P0EA0MR-000-1*
Save
This model has been saved to favorite!
View Saved List
Quote

Specifications

Hardware Capacity
12U
Heat Dissipation Capacity
40 kW with 20℃ inlet water
Dimensions (L x W x H)
Tank (1.2 m x 0.87 m x 1.56 m)
Tank + Switch (1.2 m x 0.93 m x 1.56 m)
Weight
Tank: 300 kg (w/o coolant)
CDU Power Consumption
0.6 kW
Coolant Volume
400 L
Electrical Connection
PDU: IEC 60309 32A-3P+N+E, 6H, Plug x2
Footprint
1.1 m x 0.86 m
Server Depth Supported
900 mm
Cooling Water Inlet
20°C to 35°C

[Note] The Facility Water System (FWS) loop must meet the water quality values specified in ASHRAE Liquid Cooling Guidelines for Datacom Equipment Centers, 2nd ed., Ch. 5, as reproduced in the ASHRAE TC 9.9 white paper Water-Cooled Servers: Common Designs, Components, and Processes (2019), Table 1.
Water Flow Rate
100 LPM
PUE
1.02
Ordering Information
Tank: 6NA1P0EA0MR-000-1*
IT Lift: 25FT3-000000-T0R
IT Dry Rack: 25FT5-000000-U0R
Drain Oil Pump: 25FT4-000000-K0R

[#1] All materials provided herein are for reference only. GIGABYTE reserves the right to modify or revise the content at any time without prior notice.

[#2] Advertised performance is based on maximum theoretical values as specified by the respective chipset vendors or standards organizations. Actual performance may vary depending on system configuration.

[#3] All trademarks and logos are the property of their respective owners.