Hardware Capacity
12U
Heat Dissipation Capacity
40 kW
Dimensions (L x W x H)
Tank (1.2m x 0.87m x 1.56m)
Tank + Switch (1.2m x 0.93m x 1.56m)
Weight
Tank: 300 kg (w/o coolant)
CDU Power Consumption
0.6 kW
Coolant Volume
400 L
Electrical Connection
PDU: IEC 60309 63A-3P+N+E, 6H, Plug x1
Footprint
1.1m x 0.86m
Server Depth Supported
900mm
Cooling Water Inlet
20-35°C
Water Flow Rate
100 LPM
PUE
1.02
Ordering Information
Tank: 9NA1P0EA0MR-000-001*
IT Lift: 25FT3-000000-T0R
IT Dry Rack: 25FT5-000000-U0R
Drain Oil Pump: 25FT4-000000-K0R
* The entire materials provided herein are for reference only. GIGABYTE reserves the right to modify or revise the content at anytime without prior notice.
* Advertised performance is based on maximum theoretical interface values from respective Chipset vendors or organization who defined the interface specification. Actual performance may vary by system configuration.
* All trademarks and logos are the properties of their respective holders.
* Due to standard PC architecture, a certain amount of memory is reserved for system usage and therefore the actual memory size is less than the stated amount.

RESOURCES

Back to A1P0-EA0